KMX/CA
Metal flat filter cell with U-section AISI 304 stainless steel frame and double microstretched AISI 304 stainless steel wire mesh that supports the filter fabric composed of layers of metal mesh in AISI 304 stainless steel capped braid.
TECHNICAL CHARACTERISTICS AND LIMITS OF USE
- EN ISO 16890:2016 Group ISO COARSE
(ePM1 = 1% – ePM2,5 = 2% – ePM10 = 12%) - Efficiency class (CEN EN779): G2
- Average gravimetrie efficiency:65 % for 1 O mm thick filter70 % for 23 mm thick filter75 % for 48 mm thick filter
- Maximum operating temperature: 300°c
- Relative humidity: 100 %
- Initial pressure drop:10 Pa for 10 mm thick filter20 Pa for 23 mm thick filter30 Pa for 48 mm thick filter
- Recommended final pressure drop: 250 Pa
- Maximum pressure drop: 400 Pa
- Recommended filtering velocity: 1-1,5 m/s
GREEN BUILDING
Contribute to obtain the credits of the major international rating systems for sustainable buildings:
- LEED: IP, EA, MR
- WELL: MATERIALS, COMMUNITY
- BREEAM: MAN, WST
FILTERING MEDIA
The filtering media is made up of layers of metal mesh in AISI 304 stainless steel capped braid.
APPLICATIONS
Prefiltration of high-efficiency filters, filtration of dry dust and oil mist, treatment of airborne fumes and greases.
PRODUCT DISPOSAL
Dispose of the product by separating the metal part from the filtering part. The CER code for disposal of the metal part is 120101.
Warning: declare whether the filter to be disposed of contains toxic substances.
DOWNLOAD TECHNICAL SHEET >>
Related products
-
AR10 THERM MASTERSAN
Flexible hose made of addivated polyolefin resins film reinforced with polyester mesh with anti-bacterial, anti-mildew and anti-viral material protection with steel wire helix. Thermo-insulating covering in polyester fibre (thickness 25mm/16kg/m3), outer aluminized film protection (flame retardant).
Read more -
SA10 THERM Mastersan
Flexible hose made of addivated polyolefin resins film with anti-bacterial, antimildew and anti-viral material protection with steel wire helix. Thermoinsulating covering in polyester fibre (thickness 25mm/16kg/m3). Outer aluminized film protection (flame retardant).
Read more -
DSR – DSRS
Variable geometry diffuser developped for rooms with high ceilings where a long throw and a high induction ratio are required. Made up of a housing in which individually or simultaneously adjustable deflectors are fitted (if required) in order to change the direction of the air jet in relation to the thermal conditions required.
Read more -
DAM02C
Helical-effect diffuser with helically arranged adjustable deflectors with a high induction ratio (mixing capacity) between the injected and the ambient air. Made up of a plate with holes inside which adjustable plastic deflectors are housed.
Read more
KMX/CA
Metal flat filter cell with U-section AISI 304 stainless steel frame and double microstretched AISI 304 stainless steel wire mesh that supports the filter fabric composed of layers of metal mesh in AISI 304 stainless steel capped braid.
TECHNICAL CHARACTERISTICS AND LIMITS OF USE
- EN ISO 16890:2016 Group ISO COARSE
(ePM1 = 1% – ePM2,5 = 2% – ePM10 = 12%) - Efficiency class (CEN EN779): G2
- Average gravimetrie efficiency:65 % for 1 O mm thick filter70 % for 23 mm thick filter75 % for 48 mm thick filter
- Maximum operating temperature: 300°c
- Relative humidity: 100 %
- Initial pressure drop:10 Pa for 10 mm thick filter20 Pa for 23 mm thick filter30 Pa for 48 mm thick filter
- Recommended final pressure drop: 250 Pa
- Maximum pressure drop: 400 Pa
- Recommended filtering velocity: 1-1,5 m/s
GREEN BUILDING
Contribute to obtain the credits of the major international rating systems for sustainable buildings:
- LEED: IP, EA, MR
- WELL: MATERIALS, COMMUNITY
- BREEAM: MAN, WST
FILTERING MEDIA
The filtering media is made up of layers of metal mesh in AISI 304 stainless steel capped braid.
APPLICATIONS
Prefiltration of high-efficiency filters, filtration of dry dust and oil mist, treatment of airborne fumes and greases.
PRODUCT DISPOSAL
Dispose of the product by separating the metal part from the filtering part. The CER code for disposal of the metal part is 120101.
Warning: declare whether the filter to be disposed of contains toxic substances.