Share
KMZ/A
Metal flat filter cell with U-section galvanised steel frame and double electrowelded galvanised wire mesh that supports the filter fabric made up of layers of metal mesh in aluminium steel capped braid.
TECHNICAL CHARACTERISTICS AND LIMITS OF USE
- EN ISO 16890:2016 Group ISO COARSE
(ePM1 = 1% – ePM2,5 = 2% – ePM10 = 12%) - Efficiency class (CEN EN779): G2
- Average gravimetrie efficiency:65 % for 10 mm thick filter70 % for 23 mm thick filter75 % for 48 mm thick filter
- Maximum operating temperature: 200°C
- Relative humidity: 100%
- Initial pressure drop:5 Pa for 10mm thick filter10 Pa for 23 mm thick filter15 Pa for 48 mm thick filter
- Recommended final pressure drop: 150 Pa
- Maximum pressure drop: 300 Pa
- Recommended filtering velocity: 1,5 m/s
GREEN BUILDING
Contribute to obtain the credits of the major international rating systems for sustainable buildings:
- LEED: IP, EA, MR
- WELL: MATERIALS, COMMUNITY
- BREEAM: MAN, WST
FIL TERING MEDIA
The filtering media is composed of layers of metal mesh in aluminium steel capped braid.
APPLICATIONS
Prefiltration in high-efficiency filters, filtration of dry dust and oil mist, treatment of airborne fumes and greases.
PRODUCT DISPOSAL
Dispose of the product by separating the metal part from the filtering part. The CER code for disposal of the metal partis 120101.
Warning: declare whether the filter to be disposed of contains toxic substances.
DOWNLOAD TECHNICAL SHEET >>
Related products
-
SA10 THERM Mastersan
Flexible hose made of addivated polyolefin resins film with anti-bacterial, antimildew and anti-viral material protection with steel wire helix. Thermoinsulating covering in polyester fibre (thickness 25mm/16kg/m3). Outer aluminized film protection (flame retardant).
Read more -
SA10/ESP SLEEVE Mastersan
Insulating sleeve produced with exclusive technology by TECNICA SRL.
Read more -
SA10/ESP Mastersan
Flexible hose produced with exclusive technology by TECNICA SRL.
Read more -
DCSC
Circular diffuser with adjustable cones made up of concentric truncated cone profiles, adjustable in height by means of a screw in order to change the direction of the air jet in relation to the required
Read more
KMZ/A
Metal flat filter cell with U-section galvanised steel frame and double electrowelded galvanised wire mesh that supports the filter fabric made up of layers of metal mesh in aluminium steel capped braid.
TECHNICAL CHARACTERISTICS AND LIMITS OF USE
- EN ISO 16890:2016 Group ISO COARSE
(ePM1 = 1% – ePM2,5 = 2% – ePM10 = 12%) - Efficiency class (CEN EN779): G2
- Average gravimetrie efficiency:65 % for 10 mm thick filter70 % for 23 mm thick filter75 % for 48 mm thick filter
- Maximum operating temperature: 200°C
- Relative humidity: 100%
- Initial pressure drop:5 Pa for 10mm thick filter10 Pa for 23 mm thick filter15 Pa for 48 mm thick filter
- Recommended final pressure drop: 150 Pa
- Maximum pressure drop: 300 Pa
- Recommended filtering velocity: 1,5 m/s
GREEN BUILDING
Contribute to obtain the credits of the major international rating systems for sustainable buildings:
- LEED: IP, EA, MR
- WELL: MATERIALS, COMMUNITY
- BREEAM: MAN, WST
FIL TERING MEDIA
The filtering media is composed of layers of metal mesh in aluminium steel capped braid.
APPLICATIONS
Prefiltration in high-efficiency filters, filtration of dry dust and oil mist, treatment of airborne fumes and greases.
PRODUCT DISPOSAL
Dispose of the product by separating the metal part from the filtering part. The CER code for disposal of the metal partis 120101.
Warning: declare whether the filter to be disposed of contains toxic substances.